Cat6 10 Gigabit Network Surge Protector
Model: A-10GE-48V
The model is designed to protect high-speed communication network from lightning over-voltage, transient over-voltage and static discharge. The protector implements multi-level protection circuit with advanced manufacturing process, and has excellent performance on discharge current, limiting voltage, response time, stability and over-all reliability.
FEATURES:
Multi. Protection circuits, Gas-Tube+ TVS technology
Dual protection in Common module and different module
TVS array technology, low capacitance
Multi-Strike Capability
Specification
Model |
A-10GE-POE-48V |
Electrical Parameter(Network & Power) |
Nominal operating voltage Un |
48V |
Max. continuous operating voltage Uc |
57V |
Nominal discharge current(8/20µs)In |
3kA |
Max. discharge current (8/20µs)Imax |
5KA |
Limiting voltage Up |
200V |
Line-line (@6kV, 10/700µs) |
≤150V |
Line-line (@3kA, 8/20µs) |
≤150V |
Adapt transmission rate |
10000Mbps |
Insertion loss |
≤0.5dB |
Protection line |
1-8 |
Response time tA |
1ns |
Load current |
250mA |
Application |
Cat. 6 |
Mechanical characteristics |
|
Dimension |
30(H)×87(W)×100(L)mm |
Weight per unit |
120g |
Protection grade |
IP20 |
Working conditions |
Temperature: -40 to 85ºC, |
Relative humidity: ≤95% |
Standards compliance |
CE, FCC, RoHS,ISO9001 |
INSTALLATION AND MAINTENANCE
- The SPD should be connected in series between the protected device and the signal/power transmission channel.
- The input terminal (IN) of the SPD should connect to the signal/power transmission channel, and the output terminal (OUT) of the SPD should connect to the protected device.
- Connect earthing wire of the SPD to earthing bus-bar of the lightning protection system of the room or building.
No special duty needs to be carried out for maintenance. When problem arises and the SPD is suspected, check the system with SPD taken out of circuit. Should system recover, the SPD shall be regarded as a damaged unit and must be replaced immediately.